| System Model | Energy Cuvee 100 | |
| DC Parameters | ||
| Battery Type | LFP | |
| Combination Mode | 1P112S | |
| Rated capacity | 280Ah | |
| Rated energy | 100 kWh | |
| Rated voltage | 358.4V | |
| Rated power | 50 kW | |
| Operating voltage range | 280V~408.8V | |
| Charge/discharge current | 100A / 100A | |
| Cooling Mode | Air Cooling | |
| Cycle Number | 6000 | |
| Fire Protection System | Aerosol extinguishing | |
| Detector Type | Temperature / Smoke / Water Leak | |
| PV Parameters | ||
| Maximum input power | 75 kW | |
| Maximum DC input voltage | 1000V | |
| Mppt operating voltage range | 200-850V | |
| Maximum input current | 30A×4 | |
| Rated output power | 50 kW | |
| Maximum conversion efficiency | 98.8% | |
| AC Parameters | ||
| Rated output power | 50 kW | |
| Rated voltage | 3L/N/PE; 220/380V;230/400V;240/415V | |
| Mains Frequency | 50/60 Hz | |
| Maximum output current | 83A | |
| Power Factor | 0.8 Lead... 0.8 Trailing | |
| System Parameters | ||
| Operating Environment | -20℃~50℃(Power derating 45℃+). | |
| Size (W*D*H mm) | 1130*1000*1600 | |
| Total weight | About 1.4t | |
| Protection class | IP 54 | |
| Allowable relative humidity | 0-95% | |
| Allowable altitude | ≤2000m(power derating 2000m + ). | |
| Certification Standard | IEC62619、EN62477-1、IEC 63056 | |